LC Automation
Call LC Automation on 01254 685900 +44 (0)1254 685900 E-mail LC Automation sales@lca.co.uk sales@lca.co.uk
KFD2CRG2EX1D

1 Ch.Isolated Barrier 24VDC 2Wire

1 Ch.Isolated Barrier 24VDC 2Wire
  List Price (ex VAT): £452.25  
  In stock  
  Order Code: KFD2CRG2EX1D  
  Manufacturer Code: 255620  
     

Out Of Stock? You Can Still Place Your Order.

Quantity: 
Main
Front view
Connection

Documentation:

K-System barriers Open pdf document in new window
Datasheet Open pdf document in new window

Product details


Intrinsic safety & signal conditioning

Transmitter power supply with trip point relays - 20mm


This isolated barrier is used for intrinsic safety applications. The device supplies 2-wire and 3-wire transmitters, and can also be used with current sources.

Two relays and an active 0/4mA to 20mA current source are available as outputs. The relay contacts and the current output can be integrated in security-relevant circuits. The current output is easily scaled.

On the display the measured value can be indicated in various physical units.

The device is easily configured by the use of keypad or with the PACTware configuration software.

The input has a line fault detection.

A fault is signalized by LEDs acc. to NAMUR NE44 and a separate collective error message output.

Technical specification
Supply voltage:20-35V d.c.
Power consumption:2.5W
Input/Output:Analogue input
No. of Channels:1
Output:
 Connection:0-550Ω
  Output I:Terminals 10, 11, 12
  Output II:Terminals 16, 17, 18
  Output III:Terminals 8+, 7-
 Load:≤650Ω
 Output signal:0 to 20mA or 4 to 20mA
 Output I, II:Signal relay
 Output III:Signal analogue
Input:Connection terminals 1, 2, 3
 Input I:
  Signal:0/4 to 20mA
 Input resistance:≤45Ω terminals 2, 3
 Available voltage:≥15V at 20mA
 Open circuit voltage:24V
 Short-circuit current:33mA
 Lead monitoring:Breakage I <0.2mA; short-circuit I >22mA
Ambient temperature:-20 to +60°C
Protection rating:IP20
Mounting:35mm DIN rail or panel mount
Dimensions:w40 x h119 x d115mm

Features:
  • 3 port galvanic isolation
  • Single-channel isolated barrier
  • 24V d.c. supply (power rail)
  • Input 2-wire and 3-wire transmitters and 2-wire current sources
  • Output 0/4mA to 20mA
  • 2 relay contact outputs
  • Programmable high/low alarm
  • Linearization function (max 20 points)
  • Line fault detection (LFD)
  • Up to SIL2 acc. to IEC 61508/IEC 61511
  • DIN rail/power rail solutions
  • Removable terminals reduce maintenance time
  • Fault detection and local indication