KFD2CRG2EX1D 1 Ch.Isolated Barrier 24VDC 2Wire
|
|
List Price (ex VAT): |
£452.25 |
|
|
|
In stock |
|
|
Order Code: |
KFD2CRG2EX1D |
|
|
Manufacturer Code: |
255620 |
|
|
|
|
|
Out Of Stock? You Can Still Place Your Order. |
|
| |
| |
| | | | |
|
|
Documentation:
K-System barriers
Datasheet
|
Product details
Intrinsic safety & signal conditioning
Transmitter power supply with trip point relays - 20mm
This isolated barrier is used for intrinsic safety applications. The device supplies 2-wire and 3-wire transmitters, and can also be used with current sources.
Two relays and an active 0/4mA to 20mA current source are available as outputs. The relay contacts and the current output can be integrated in security-relevant circuits. The current output is easily scaled.
On the display the measured value can be indicated in various physical units.
The device is easily configured by the use of keypad or with the PACTware configuration software.
The input has a line fault detection.
A fault is signalized by LEDs acc. to NAMUR NE44 and a separate collective error message output.
Technical specification
| Supply voltage: | 20-35V d.c.
| Power consumption: | 2.5W
| Input/Output: | Analogue input
| No. of Channels: | 1
| Output:
Connection: | 0-550Ω
| Output I: | Terminals 10, 11, 12
| Output II: | Terminals 16, 17, 18
| Output III: | Terminals 8+, 7-
| Load: | ≤650Ω
| Output signal: | 0 to 20mA or 4 to 20mA
| Output I, II: | Signal relay
| Output III: | Signal analogue
| Input: | Connection terminals 1, 2, 3
| Input I:
Signal: | 0/4 to 20mA
| Input resistance: | ≤45Ω terminals 2, 3
| Available voltage: | ≥15V at 20mA
| Open circuit voltage: | 24V
| Short-circuit current: | 33mA
| Lead monitoring: | Breakage I <0.2mA; short-circuit I >22mA
| Ambient temperature: | -20 to +60°C
| Protection rating: | IP20
| Mounting: | 35mm DIN rail or panel mount
| Dimensions: | w40 x h119 x d115mm | | |
Features:
3 port galvanic isolation
Single-channel isolated barrier
24V d.c. supply (power rail)
Input 2-wire and 3-wire transmitters and 2-wire current sources
Output 0/4mA to 20mA
2 relay contact outputs
Programmable high/low alarm
Linearization function (max 20 points)
Line fault detection (LFD)
Up to SIL2 acc. to IEC 61508/IEC 61511
DIN rail/power rail solutions
Removable terminals reduce maintenance time
Fault detection and local indication
|
|
|