Product details


Intrinsic safety & signal conditioning

Temperature converter with trip point relay and display


This signal conditioner provides the galvanic isolation between field circuits and control circuits.

The device converts the signal of a resistance thermometer, thermocouple, potentiometer, or voltage source to a proportional output current. It also provides a relay trip value.

The removable terminal block K-CJC-** is available as an accessory for internal cold junction compensation of thermocouples.

A fault is signalized by LEDs acc. to NAMUR NE44 and a separate collective error message output.

The device is easily configured by the use of the PACTware™ configuration software.

Technical specification
Supply voltage:20-30V d.c.
Power loss:≤2W
Power consumption:2.2W
No. of channels:1
Input/output:Analogue input
Output:
 Output I, II:Relay
 Output III:Analogue current output
Input:
 RTD:Pt100, Pt500, Pt1000, Ni100, Ni1000
  Type of measuring:2-, 3-, 4-wire technology
  Line resistance:≤50Ω
  Measuring circuit monitoring:Sensor burnout, sensor short-circuit
 Thermocouples:Type B, E, J, K, L, N, R, S, T
  Cold junction compensation:External and internal
  Measuring circuit monitoring:Sensor burnout
 Voltage:0-10V, 2-10V, 0-1V,
-100-100mV
 Potentiometer:0.8-20kΩ
  Types of measuring:2-, 3-, 5-wire technology
 Input resistance:≥250kΩ (0-10V),
≥1MΩ (0-1V, -10-100mV)
 Measuring current:Approx. 400μA with resistance
 measuring sensor
Ambient temperature:-20 to +60°C
Protection rating:IP20
Mounting:35mm DIN rail or panel mount
Dimensions:w40 x h119 x d115mm

Features:
  • 3 port isolation
  • Single-channel signal conditioner
  • 24V d.c. supply (power rail)
  • Thermocouple, RTD, potentiometer or voltage input
  • Redundant TC input
  • Current output 0/4-20mA
  • 2 relay contact outputs
  • Configurable by PACTware™
  • Line fault (LFD) and sensor burnout detection
  • Up to SIL2 acc. to IEC 61508/IEC 61511
  • Limit detection with dual form C alarm contacts
  • Removable terminals reduce maintenance time
  • Fault detection and alarming


  • PLEASE NOTE: This device is not suitable for use in hazardous areas